Re: Smiley Power
I can throw my 110v 15amp breakers if I want too on my 40amp riland clone, esiepcially plasma cutting. with the plasma you can throw them pretty easily at half way. you pretty much have to turn it up all the way welding. I've never thrown a 20 or 30amp 220v breaker downstairs tho...
#5
Re: Smiley Power
well it keeps kicking a 30 amp breaker downstairs. I'm running a 16 ft exstension cord that we use to back feed our generator through the 220 when we need to via the drier outlet ( We disconect the main so we don't kill anyone ) . I'm too tired to ---- w/ it right now.
#7
Re: Smiley Power
Alright I was tired. This is how it's wired up.
So I'm going from the machine which has 4ft. of 10 gauge wire to my hubble plug. This is plugged into a 35ft 10-3 line ( 10 gauge) which plugs into the drier outlet. Then the misc. amount from the upstairs to dowstair breaker.
So should I try for a 50 amp breaker or go for a whole new extension cord?
So I'm going from the machine which has 4ft. of 10 gauge wire to my hubble plug. This is plugged into a 35ft 10-3 line ( 10 gauge) which plugs into the drier outlet. Then the misc. amount from the upstairs to dowstair breaker.
So should I try for a 50 amp breaker or go for a whole new extension cord?
#10
Re: Smiley Power
So I hooked the welder up with a plug so it could run of a generator. So it has the 4ft of 10g wire that came with the welder, to the plug, which is plugged into the generator. It ran off of the generator no problem. The generator only has a 25 amp breaker.
So thinking it was the big *** extension cord I hooked the welder with the 4ft of 10g wire straight to a drier plug and dried that to see if it kicked it. Sure enough it kicked the 30 amp breaker.
So either the breaker is fucked. Or the wiring to the breaker box is too small.
So thinking it was the big *** extension cord I hooked the welder with the 4ft of 10g wire straight to a drier plug and dried that to see if it kicked it. Sure enough it kicked the 30 amp breaker.
So either the breaker is fucked. Or the wiring to the breaker box is too small.