Default What amperage should I use for welder/compressor? (HMT electricians)

I've got an air compressor and a 120v MIG welder, both of which draw 15 amps.

I'm running them a pre-existing 15 amp circuit, whcih also controls a few rooms in the house. Unless I turn off all the lights, the welder/compressor tend to trip the breaker really fast (no ----, huh?), and if I do have a light on, it tends to dim it very badly. I've decided to run a dedicated line from my breaker box, which should be an easy shot.

I don't plan on running both of these at the same time, so I'm thinking 20 amp. There may be a time in which the compressor motor would be on and I would be needing to use an electric grinder or sander or something, so would you guys opt for 20 amp service, or should I just upgrade for a 30 amp service and just not ---- with it ever again? I'll be running 12/2 if I go 20 amp, or 10/2 if I run 30 amp. Will this wire be sufficient for what I'm doing? Thanks guys.
USS is offline  
Old 06-14-2006, 10:45 PM
  #2  
3.0 BAR
 
hotrex's Avatar
 
Join Date: Dec 2002
Posts: 12,568
Default Re: What amperage should I use for welder/compressor? (HMT electricians)

20 amp breaker should be fine

just remember to check the ga of the wire.

you cant just up the size of the breaker without rewiring the outlets with a bigger ga wire.

hotrex is offline  
Old 06-14-2006, 10:46 PM
  #3  
3.0 BAR
 
hotrex's Avatar
 
Join Date: Dec 2002
Posts: 12,568
Default Re: What amperage should I use for welder/compressor? (HMT electricians)

why not just go apeshit, run a 50a breaker and some 8ga wire.

u can run your neighors tools too.
hotrex is offline  
Old 06-14-2006, 10:50 PM
  #4  
USS
0.0 BAR
Thread Starter
 
USS's Avatar
 
Join Date: Oct 2004
Posts: 0
Default Re: What amperage should I use for welder/compressor? (HMT electricians)

Originally Posted by hotrex
why not just go apeshit, run a 50a breaker and some 8ga wire.

u can run your neighors tools too.
haha, I could do that, but I don't think we got any 8 ga left from the remodel.

Yeah, I think I'll go 30 amp. It's more than I need, but ---- it, I don't want to have any issues. Will 12/2 be cool on a 30 amp breaker, or will I have to run some 10/2?
USS is offline  
Old 06-14-2006, 11:39 PM
  #5  
3.0 BAR
 
Dr.Boost's Avatar
 
Join Date: Mar 2003
Posts: 21,479
Default Re: What amperage should I use for welder/compressor? (HMT electricians)

10-2 for 30amp, although at that rate you might have issues with your tools if they ever have a problem(tool shorts out and doesn't trip the breaker).

I would just use 12-2 and a 20a breaker. It's safer and I highly doubt you'll have any issues since it will be it's own dedicated circuit.
__________________
Best Car Insurance | Auto Protection Today | FREE Trade-In Quote
Dr.Boost is offline  
Old 06-14-2006, 11:48 PM
  #6  
USS
0.0 BAR
Thread Starter
 
USS's Avatar
 
Join Date: Oct 2004
Posts: 0
Default Re: What amperage should I use for welder/compressor? (HMT electricians)

Originally Posted by Dr.Boost
10-2 for 30amp, although at that rate you might have issues with your tools if they ever have a problem(tool shorts out and doesn't trip the breaker).

I would just use 12-2 and a 20a breaker. It's safer and I highly doubt you'll have any issues since it will be it's own dedicated circuit.
Thanks. 12-2 and a 20 amp breaker it is.
USS is offline  
Old 06-15-2006, 10:34 AM
  #7  
3.0 BAR
 
BoosTedZSix's Avatar
 
Join Date: Jan 2004
Posts: 5,708
Default Re: What amperage should I use for welder/compressor? (HMT electricians)

i believe thats what it is in my house right now. Compressor never trips the breaker. Although i had this one instance where it kept tripping when i was trying to plug my light in. Turns out the bulb was shorted
BoosTedZSix is offline  
Related Topics
Thread
Thread Starter
Forum
Replies
Last Post
Donald125
General Discussion
14
04-24-2007 09:04 PM
MikeJ-2009
General Discussion
53
02-07-2006 12:17 AM
Alex in Houston
Fabrication
25
12-29-2005 09:25 AM
IO_303
Hybrid/Tech
1
03-19-2005 10:02 PM


Thread Tools
Search this Thread
Quick Reply: What amperage should I use for welder/compressor? (HMT electricians)



All times are GMT -5. The time now is 07:37 PM.